Study guides ยท Stuff Every HVAC Tech Should Know

Aha Trivia

Stuff Every HVAC Tech Should Know: Training Guide

This guide teaches the EPA Section 608 refrigerant certification topics, from ozone chemistry and refrigerant families to recovery targets, leak repair rules, and low-pressure chiller service.

Who this is for: It is for new HVAC technicians and curious adult learners who want to understand EPA refrigerant rules and prepare for the Section 608 certification tests.

Study aid, not authority. This guide is not an official course, a certificate or a license. This guide uses only the listed EPA and manufacturer source facts. It is not official legal advice or a safety manual. For a specific job, health, safety, or legal decision, ask your employer, an EPA-approved certifying program, or a qualified professional.

Written by Aha Trivia from 102 checked cards and 35 sources. Checked 2026-10-25.

โ–ถ Practice in Aha Trivia About this deck

Key facts

Ozone layer
Most ozone is in the stratosphere, about 15 to 30 km up. Basic Ozone Layer Science, US EPA
Chlorine damage
One chlorine atom can destroy over 100,000 ozone molecules. Basic Ozone Layer Science, US EPA
ODP
ODP compares a chemical to CFC-11, defined as 1.0. Ozone-Depleting Substances, US EPA
GWP
A GWP of 700 means 700 times the climate effect of the same mass of carbon dioxide. Frequent Questions on the Phasedown of Hydrofluorocarbons, US EPA
Venting ban
Intentional venting of HFC refrigerant during service is banned. Stationary Refrigeration and Air Conditioning (Section 608), US EPA
Cylinder fill
Refrigerant cylinders should be filled to no more than 80 percent of their volume. Robinair RG6 Recovery Unit Operating Manual

Study plan

  1. Week 1: Learn what refrigerants are and how they affect the ozone layer and climate.
    Lessons: Ozone, Climate and Refrigerant Families
  2. Week 2: Learn the main EPA laws, phaseouts, and certification rules.
    Lessons: EPA Laws, Phaseouts and Certification Basics
  3. Week 3: Learn how to recover, recycle, reclaim, and handle refrigerants safely.
    Lessons: Recovery, Recycling and Safe Service
  4. Week 4: Learn the Type I small appliance rules and recovery targets.
    Lessons: Type I Small Appliances
  5. Week 5: Learn Type II high and medium pressure recovery and leak repair rules.
    Lessons: Type II High and Medium Pressure Recovery and Leak Repair
  6. Week 6: Learn Type III low pressure service, sales, records and technology transition rules.
    Lessons: Type III Low Pressure Service and Business Rules

Lesson 1 of 6

Ozone, Climate and Refrigerant Families

This lesson explains the ozone layer, how chlorine damages it, ODP and GWP, refrigerant families, and the basic refrigeration loop.

What you will learn

  • Explain how chlorine damages the ozone layer.
  • Define ODP and GWP.
  • Name the main refrigerant families and their chlorine content.
  • Describe the four main parts of a basic refrigeration loop.

The ozone shield and chlorine damage

Most of the atmosphere's ozone sits in the stratosphere, a layer about 15 to 30 km above the ground. That layer soaks up much of the sun's harmful ultraviolet light before it reaches us.

A single chlorine atom can destroy over 100,000 ozone molecules before it leaves the stratosphere, because chlorine is not used up in the reaction. Leaked CFC or HCFC refrigerant can therefore do long-lasting damage.

Ozone depletion potential, or ODP, compares a chemical to CFC-11, which is defined as 1.0. A bigger ODP means more ozone damage, and zero means none.

HFC refrigerants have an ODP of zero because they do not contain chlorine. But some HFCs are strong greenhouse gases, which is a separate climate problem.

Refrigerant families and climate impact

EPA's test topics name R-12 as a CFC, R-22 as an HCFC, and R-134 as an HFC. CFCs and HCFCs contain chlorine, so they can deplete ozone. HFCs do not.

Global warming potential, or GWP, compares a gas to carbon dioxide, which has a GWP of 1. A refrigerant with a GWP of 700 traps heat 700 times as strongly per kilogram as carbon dioxide.

R-32 and R-454B are classed A2L, which means they are mildly flammable. They need extra care around ignition sources.

There are no true drop-in replacement refrigerants. Blend refrigerants also undergo fractionation, meaning the blend's components leak at different rates, so the remaining charge may no longer have the original mix.

The basic compression refrigeration loop

The compressor takes in low-pressure refrigerant vapor and squeezes it to a high pressure and high temperature, which requires work input.

In an air-cooled system, the condenser gives up heat to the outdoor air. There the hot refrigerant vapor changes from superheated vapor to sub-cooled liquid.

The evaporator is where low-pressure refrigerant boils and absorbs heat from the air or space being cooled. This is the actual cooling step.

The expansion valve drops the refrigerant's pressure before it enters the evaporator. Some liquid flashes to vapor, so the refrigerant leaves the valve as a mix of liquid and vapor.

Pressure measurements and special refrigerants

A gauge reads pressure above atmospheric pressure. To convert a psig reading to absolute psia, add about 14.7 psi, which is standard atmospheric pressure at sea level.

Standard atmospheric pressure is 29.9 inches of mercury. Absolute pressure counts from a perfect vacuum, so it is the value to use with temperature-pressure charts.

Mildly flammable A2L refrigerants such as R-32 and R-454B must be handled carefully. Technicians must keep potential ignition sources away during service.

Numbers to remember

ItemValueSource
Stratosphere altitude15 to 30 kmBasic Ozone Layer Science, US EPA
ODP of CFC-111.0Ozone-Depleting Substances, US EPA
GWP of 700700 times the climate effect of CO2Frequent Questions on the Phasedown of Hydrofluorocarbons, US EPA
Atmospheric pressure to add14.7 psiSection 608 Technician Certification Test Topics, US EPA

Knowledge check

Choose an answer before reading the answer key.

  1. What role does the stratosphere's ozone layer play?

    1. It traps heat like a greenhouse gas
    2. It absorbs much of the sun's harmful ultraviolet light
    3. It reflects sunlight back into space
    4. It supplies oxygen for breathing
  2. Why can one chlorine atom destroy so many ozone molecules?

    1. It is not used up in the reaction
    2. It reacts with water
    3. It multiplies in sunlight
    4. It stays in the troposphere
  3. Which refrigerant family has an ozone depletion potential of zero?

    1. Halons
    2. HCFC
    3. CFC
    4. HFC
  4. In the basic loop, where does refrigerant boil and absorb heat from the air being cooled?

    1. Expansion valve
    2. Condenser
    3. Evaporator
    4. Compressor
  5. What does a refrigerant with a GWP of 700 mean?

    1. 700 degrees warmer
    2. 700 times the climate effect of CO2
    3. It lasts 700 years
    4. It depletes ozone 700 times

Answer key

  1. B. It absorbs much of the sun's harmful ultraviolet light. Ozone in the stratosphere soaks up much of the sun's harmful ultraviolet light before it reaches us. Basic Ozone Layer Science, US EPA
  2. A. It is not used up in the reaction. Chlorine is not used up when it breaks apart an ozone molecule, so it keeps going. Basic Ozone Layer Science, US EPA
  3. D. HFC. HFCs do not contain chlorine, so they do not attack the ozone layer. Ozone-Depleting Substances, US EPA
  4. C. Evaporator. The evaporator is where low-pressure refrigerant boils and absorbs heat. Refrigeration 201, US EPA (archived)
  5. B. 700 times the climate effect of CO2. GWP compares heat-trapping strength to carbon dioxide, which has a GWP of 1. Frequent Questions on the Phasedown of Hydrofluorocarbons, US EPA

Sources for this lesson

Lesson 2 of 6

EPA Laws, Phaseouts and Certification Basics

This lesson explains the Montreal Protocol, US phaseouts, Section 608, the venting prohibition, and basic certification and sales rules.

What you will learn

  • Name major ozone and HFC phaseout milestones.
  • Explain Section 608 and the venting prohibition.
  • Identify who needs certification and who issues it.
  • Describe basic refrigerant sales and equipment documentation rules.

International and US phaseout milestones

Countries signed the Montreal Protocol in 1987 as the first step in international efforts to protect stratospheric ozone.

The Kigali Amendment to the Montreal Protocol extended controls to phase down HFCs, which do not harm ozone but can warm the climate.

In the US, the ban on producing and importing CFCs took effect on January 1, 1996. Halon production and import had already been banned on January 1, 1994.

Since 2020 there has been no new production or import of R-22 in the US. All HCFCs end in 2030.

The AIM Act requires US HFC production and use to fall by 85 percent from baseline by 2036. EPA started the phasedown with a 10 percent reduction in 2022 and dropped to 60 percent of baseline in 2024.

Section 608 and the venting prohibition

Section 608 of the Clean Air Act created the National Recycling and Emission Reduction Program. It is why technicians need certification, must recover refrigerant, and cannot vent it.

The venting ban in Section 608 covers both ozone-depleting refrigerants and their substitutes, including HFCs. Any work that maintains, services, repairs or disposes of equipment must recover the refrigerant instead of releasing it.

Installing an R-410A mini-split, even just connecting pre-charged lines, requires Section 608 certification.

The venting rule lists a few exempt substitutes, including carbon dioxide, nitrogen and water in any application. Refrigerants like R-134a and R-22 are not exempt.

Once refrigerant has been recovered, knowingly releasing it is a violation of the venting prohibition. Small accidental losses during a good-faith recovery can be de minimis, but only when the technician follows required recovery practices.

Certification and personnel

Certification types match appliance categories: Type I for small appliances, Type II for medium, high and very high-pressure equipment, Type III for low-pressure equipment. A technician who works on all categories needs Universal. EPA does not offer a separate R-410A certification; certification is by appliance type, not refrigerant.

An apprentice can work on refrigerant circuits without their own certification for up to two years after first registering. During that time, a certified technician with the correct certification must closely and continually supervise the apprentice.

Certification cards come from the EPA-approved organization that tested and certified you, not from EPA. If you lose the card, contact that organization for a replacement.

Under EPA's sales restriction, a seller may legally sell refrigerant for use in equipment only to a certified technician, or to a buyer who employs one and can show proof.

Recovery and recycling machines must be certified through an EPA-approved third-party testing organization. They must also have low-loss fittings on all hoses.

Documentation basics

Technicians must keep records of refrigerant recovered from disposed appliances holding 5 to 50 pounds for three years. An employer can keep them for its technicians.

On appliances that normally hold 50 or more pounds of ozone-depleting refrigerant, the technician must give the customer an invoice showing the amount of refrigerant added.

A standing pressure decay test alone shows that leaking is happening, but it does not show where the leak is. It must be paired with a method that locates the leak, such as an ultrasonic test, gas-imaging camera or bubble test.

Connecting or disconnecting hoses and gauges to read pressures is not considered opening an appliance, but it still requires Section 608 certification.

Numbers to remember

ItemValueSource
Montreal Protocol signing year1987International Treaties and Cooperation about the Protection of the Stratospheric Ozone Layer, US EPA
US CFC production and import ban year1996Phaseout of Class I Ozone-Depleting Substances, US EPA
US R-22 production and import ban year2020Phaseout of Class II Ozone-Depleting Substances, US EPA
AIM Act HFC reduction by 203685 percentFrequent Questions on the Phasedown of Hydrofluorocarbons, US EPA
Disposal record retention3 yearsEPA Q&A for Section 608 Certified Technicians

Knowledge check

Choose an answer before reading the answer key.

  1. What is the main goal of the program created by Section 608?

    1. Regulate motor vehicle air conditioners
    2. Phase out all refrigerants
    3. Reduce refrigerant emissions and require recycling
    4. Set fuel economy standards
  2. A tech recovers R-410A and knowingly releases it afterward. What is this?

    1. A legal transfer
    2. A recycling step
    3. A venting violation
    4. A de minimis release
  3. If a technician loses their Section 608 card, who should they contact?

    1. EPA
    2. Their employer
    3. State licensing board
    4. The certifying organization
  4. What must a seller verify before selling refrigerant for use in equipment?

    1. The buyer owns a truck
    2. The buyer is a homeowner
    3. The buyer has a business license
    4. The buyer is certified or employs a certified technician
  5. How long must disposal records for appliances holding 5 to 50 pounds be kept?

    1. Three years
    2. Ten years
    3. One year
    4. Five years

Answer key

  1. C. Reduce refrigerant emissions and require recycling. Section 608 is the National Recycling and Emission Reduction Program, which aims to reduce emissions and promote recycling. Stationary Refrigeration and Air Conditioning (Section 608), US EPA
  2. C. A venting violation. Once refrigerant has been recovered, knowingly letting it out is a violation of the venting prohibition. 40 CFR 82.154 Prohibitions (Cornell LII)
  3. D. The certifying organization. EPA does not issue certification cards. The organization that certified the technician issues and replaces them. Section 608 Technician Certification, US EPA
  4. D. The buyer is certified or employs a certified technician. Sellers must verify that the buyer is certified or employs at least one certified technician and can show proof. EPA Refrigerant Sales Restriction
  5. A. Three years. EPA requires these disposal records to be kept for three years. EPA Q&A for Section 608 Certified Technicians

Sources for this lesson

Lesson 3 of 6

Recovery, Recycling and Safe Service

This lesson covers the Three Rs, cylinder safety, evacuation, leak testing, and handling hazards for refrigerants.

What you will learn

  • Define recover, recycle and reclaim.
  • Explain cylinder fill limits and disposal rules.
  • Describe safe leak test and evacuation practices.
  • Identify refrigerant exposure and A2L hazards.

The Three Rs

To recover means to remove refrigerant in any condition and store it in an external container, with no testing or processing.

To recycle means to extract refrigerant and clean it for reuse in equipment owned by the same owner, usually by oil separation and filter-driers.

To reclaim means to reprocess recovered refrigerant to new-product purity specifications, verified by analysis. Only then can it be sold.

Technicians need to avoid mixing different refrigerants together. A mixed batch may not be reclaimable because each refrigerant must meet its own purity specs.

Cylinders and pressure safety

A refrigerant cylinder should be filled to no more than 80 percent by volume. The empty 20 percent is called head pressure room, and it gives the liquid room to expand when it warms.

Reusable recovery cylinders must be DOT approved and use the yellow and gray color code. Disposable cylinders must never be refilled.

DOT rules for liquefied gas cylinders say the liquid portion must never completely fill the cylinder at temperatures up to 131 F. A liquid-full cylinder has no room for expansion and can burst.

For leak testing, use dry nitrogen rather than oxygen or compressed air. Nitrogen is the best leak test gas for EPA's Type 2 outline.

When pressurizing a system with nitrogen, use a pressure regulator and a relief valve. The regulator sets a safe test pressure, and the relief valve lets gas out if pressure climbs too high.

Evacuation and moisture control

A vacuum pump removes air and moisture from a system at the end of service before it is charged.

Polyolester oil, or POE oil, absorbs moisture very quickly. Keep line set caps on until you connect them, because leaving lines open means extra evacuation to remove moisture.

Keep the refrigerant system closed as much as possible when working with HFC systems and POE oil.

On an HFC system with POE oil, leaving the refrigerant lines open means you will need extra evacuation to remove the moisture the oil absorbs.

Exposure and A2L safety

Refrigerant exposure can cause oxygen deprivation, cardiac effects, frostbite and long-term hazards. Equipment room requirements include an oxygen deprivation sensor with all refrigerants.

A halide torch or any other leak detector using a naked flame must never be used on a system with a mildly flammable A2L refrigerant. Use bubble solutions or suitable electronic detectors.

If a leak is suspected on an A2L system, all naked flames must be removed or extinguished.

Under EPA's 2024 rule, a 608-certified tech may evacuate a disposable cylinder to 15 inches of mercury before disposal instead of refilling it.

Numbers to remember

ItemValueSource
Maximum cylinder fill by volume80 percentRobinair RG6 Recovery Unit Operating Manual
Head pressure room20 percentRobinair RG6 Recovery Unit Operating Manual
Disposable cylinder evacuation level15 inches of mercuryEmissions Reduction and Reclamation Program fact sheet, US EPA
One Lennox nitrogen regulator setting160 psigLennox installation instructions 508844-01 (R-454B split system)
One Lennox first evacuation target23,000 microns, about 29.01 inches of mercuryLennox installation instructions 508844-01 (R-454B split system)

Knowledge check

Choose an answer before reading the answer key.

  1. What does it mean to recover refrigerant?

    1. Clean it for same-owner use
    2. Burn it safely
    3. Remove it and store it in an outside container
    4. Reprocess it to new-product purity
  2. Which term means cleaning recovered refrigerant for reuse in the same owner's equipment?

    1. Replace
    2. Recycle
    3. Reclaim
    4. Recover
  3. Why is it unsafe to fill a refrigerant cylinder completely?

    1. The liquid needs room to expand when it warms
    2. The cylinder may become too heavy
    3. The refrigerant will boil at room temperature
    4. The pressure will drop too low
  4. Why should line set caps stay on until connection on an HFC system with POE oil?

    1. The caps prevent overcharging
    2. The caps are required by DOT
    3. POE oil absorbs moisture very quickly
    4. The caps keep out refrigerant

Answer key

  1. C. Remove it and store it in an outside container. Recovery removes refrigerant in any condition and stores it in an external container. 40 CFR 82.152 Definitions (Cornell LII)
  2. B. Recycle. Recycling cleans recovered refrigerant for reuse by the same owner. 40 CFR 82.152 Definitions (Cornell LII)
  3. A. The liquid needs room to expand when it warms. Liquid refrigerant expands as it warms, so a completely full cylinder could burst. Robinair RG6 Recovery Unit Operating Manual
  4. C. POE oil absorbs moisture very quickly. Polyolester oil soaks up moisture fast, and open lines lead to extra evacuation. Lennox installation instructions 508844-01 (R-454B split system)

Sources for this lesson

Lesson 4 of 6

Type I Small Appliances

This lesson covers EPA's small appliance definition, Type I recovery targets, vacuum alternatives, and service rules for small appliances.

What you will learn

  • Define a small appliance.
  • Explain recovery percentages and the vacuum alternative.
  • Describe tools and access fittings for dead compressors.
  • State who does not need certification for disposal only.

Small appliance definition and access

EPA defines a small appliance as a factory-sealed unit with five pounds or less of refrigerant. Examples include home refrigerators, window air conditioners, vending machines, dehumidifiers, under-the-counter ice makers and drinking water coolers.

A factory-sealed window air conditioner counts as a small appliance under EPA's definition.

A process stub is a short resealable tube on a small appliance or room air conditioner that gives a technician access to the refrigerant.

A person who only disposes of small appliances does not need Section 608 certification. But servicing or repairing a small appliance, such as attaching gauges, does require Type I or higher certification.

Recovery targets

Using recovery equipment made on or after November 15, 1993, recover 90 percent when the small appliance's compressor is running.

If the compressor is not working, the target drops to 80 percent with post-1993 recovery equipment.

Instead of recovering a percentage, a technician can evacuate a small appliance to four inches of mercury vacuum.

Using recovery equipment made before November 15, 1993, recover 80 percent of the refrigerant, whether the compressor is working or not.

The small appliance recovery rules apply both before opening a small appliance and when disposing of one.

Techniques and tools

System-dependent recovery equipment, also called passive equipment, needs components in the appliance to help remove the refrigerant. Self-contained equipment has its own means, so it works without the appliance's help.

When recovering from a small appliance with an inoperative compressor, install both high-side and low-side access valves. Run a working compressor when using a passive system-dependent recovery device.

Remove solderless access fittings after finishing a small appliance service. They are temporary tools for getting to the refrigerant.

Small-appliance recovery equipment itself must be certified to recover 90 percent with the test stand compressor running and 80 percent with it off.

Mail-in Type I tests have a passing score of 84 percent, and they cannot count toward a Universal certification. Training material sent with mail-in Type I tests may not include sample questions that mimic the real test.

Numbers to remember

ItemValueSource
Small appliance max charge5 pounds40 CFR 82.152 Definitions (Cornell LII)
Post-1993 working compressor recovery90 percent40 CFR 82.156 (Cornell LII)
Post-1993 dead compressor recovery80 percent40 CFR 82.156 (Cornell LII)
Vacuum alternative4 inches of mercury40 CFR 82.156 (Cornell LII)
Pre-1993 equipment recovery80 percent40 CFR 82.156 (Cornell LII)
Mail-in Type I passing score84 percent40 CFR Part 82 Subpart F Appendix D, certifying programs (Cornell LII)

Knowledge check

Choose an answer before reading the answer key.

  1. Which of these counts as a small appliance?

    1. Supermarket rack
    2. Window air conditioner
    3. Rooftop unit
    4. Office chiller
  2. With post-1993 recovery equipment and a working compressor, what must you recover?

    1. 84 percent
    2. 80 percent
    3. 90 percent
    4. 70 percent
  3. With post-1993 recovery equipment and a dead compressor, what must you recover?

    1. 70 percent
    2. 90 percent
    3. 84 percent
    4. 80 percent
  4. Instead of recovering a percentage, what vacuum can you use on a small appliance?

    1. Four inches of mercury
    2. Twenty inches
    3. Fifteen inches
    4. Ten inches
  5. For an inoperative compressor, which access valves does EPA say to install?

    1. Both high-side and low-side
    2. High-side only
    3. Low-side only
    4. Neither

Answer key

  1. B. Window air conditioner. EPA lists room air conditioners, including window units, as small appliances. 40 CFR 82.152 Definitions (Cornell LII)
  2. C. 90 percent. Post-1993 equipment with a working compressor has a 90 percent target. 40 CFR 82.156 (Cornell LII)
  3. D. 80 percent. A broken compressor cannot help push refrigerant out, so the target lowers to 80 percent. 40 CFR 82.156 (Cornell LII)
  4. A. Four inches of mercury. EPA allows a four-inch mercury vacuum as an alternative to a percentage. 40 CFR 82.156 (Cornell LII)
  5. A. Both high-side and low-side. A dead compressor cannot move refrigerant, so passive recovery needs access to both sides. EPA Section 608 Technician Certification Test Topics

Sources for this lesson

Lesson 5 of 6

Type II High and Medium Pressure Recovery and Leak Repair

This lesson covers high, medium and very high pressure classes, recovery vacuum levels, major repairs, and leak repair rules.

What you will learn

  • Classify high, medium, very high and low pressure refrigerants.
  • State required evacuation levels for Type II recovery.
  • Explain major repairs and safe opening practices.
  • Apply leak repair triggers and deadlines.

Pressure classes and recovery levels

EPA calls a refrigerant high-pressure if its liquid saturation pressure at 104 F falls between 170 and 355 psia. Very high-pressure is above 355 psia, or a critical temperature below 104 F. Medium-pressure is 45 to 170 psia, and low-pressure is below 45 psia.

R-410A, R-22, R-407A, R-407C and R-502 are examples of high-pressure refrigerants. R-134a belongs to the medium-pressure class, and R-11 and R-123 are low-pressure refrigerants.

For a medium-pressure appliance under 200 pounds, post-1993 recovery equipment must evacuate to 10 inches of mercury vacuum.

For a high-pressure appliance under 200 pounds, post-1993 recovery equipment must evacuate to 0 inches of mercury vacuum, which is atmospheric pressure.

A high-pressure appliance with 200 pounds or more must reach 10 inches of mercury vacuum with post-1993 equipment.

For a non-major repair where the appliance will not be evacuated to the atmosphere afterward, evacuate to no higher than 0 psig before opening.

Major repairs and safe opening

EPA says a repair is major if it involves removing the compressor, condenser, evaporator or auxiliary heat exchange coil. Major repairs require evacuating to the Table 1 levels.

A repair that uncovers an opening of more than four square inches of flow area for more than 15 minutes is also major.

After reaching the required recovery vacuum, wait a few minutes to see if system pressure rises. A rise means there is still liquid refrigerant in the system or in the oil.

Never energize a hermetic compressor while it is under a vacuum. Powering one up while the system is evacuated is unsafe.

System-dependent recovery equipment may not be used on appliances holding more than 15 pounds of refrigerant, unless it is a pump-out unit permanently attached to the appliance.

Leak repair rules for large appliances

Section 608 leak repair rules apply to appliances with a full charge of at least 50 pounds of an ozone-depleting refrigerant. Since April 10, 2020, they do not apply to appliances containing only substitute refrigerants such as HFCs.

EPA's 2024 HFC leak repair rule applies to appliances holding at least 15 pounds of an HFC or substitute with a GWP above 53. Residential and light commercial AC and heat pumps are excluded.

Commercial refrigeration, such as supermarket and cold storage systems, triggers repair at a leak rate over 20 percent per year. Industrial process refrigeration triggers at 30 percent, and comfort cooling triggers at 10 percent.

Owners must identify and repair leaks within 30 days. If the repair needs an industrial process shutdown, the period is 120 days. Parts availability extensions are capped at 180 days, or 270 days with an industrial process shutdown.

A follow-up verification test must be done within 10 days of the successful initial test. Both tests must show the repair worked.

Commercial and industrial process systems with a full charge of 500 pounds or more need leak inspections every three months. These quarterly inspections continue until leak rate calculations show no excess for four quarters in a row. Commercial and industrial systems of 50 to 499 pounds, and comfort cooling, need yearly inspections, and those continue until a full year passes below the leak-rate threshold.

Plans, reports and definitions

An owner who chooses to retire or retrofit a leaking appliance must create a plan within 30 days and finish the work within one year of the plan's date. The plan must be signed and kept at the site.

Owners of appliances holding 50 or more pounds that leak 125 percent or more of their charge in a calendar year must send EPA a report by March 1 of the following year.

EPA defines leak rate as the percent of the full charge that would be lost over 12 months if the current rate of loss continued. Facilities can use the annualizing method or the rolling average method, but must use the same one for all appliances.

To mothball an appliance means to evacuate it to at least atmospheric pressure and temporarily shut it down. The leak repair clock pauses while it is mothballed and restarts when refrigerant is added again.

Connecting and disconnecting hoses and gauges to read pressure is not considered opening an appliance.

Numbers to remember

ItemValueSource
High-pressure saturation range170 to 355 psia40 CFR 82.152 Definitions (Cornell LII)
Medium under 200 target10 inches of mercury vacuum40 CFR 82.156 (Cornell LII)
High under 200 target0 inches of mercury vacuum40 CFR 82.156 (Cornell LII)
High 200 or more target10 inches of mercury vacuum40 CFR 82.156 (Cornell LII)
Commercial refrigeration leak trigger20 percent per year40 CFR 82.157 Appliance maintenance and leak repair (Cornell LII)
Repair deadline30 days40 CFR 82.157 Appliance maintenance and leak repair (Cornell LII)

Knowledge check

Choose an answer before reading the answer key.

  1. Which refrigerant is an example of a high-pressure refrigerant?

    1. R-123
    2. R-134a
    3. R-11
    4. R-410A
  2. For a medium-pressure appliance under 200 pounds with post-1993 equipment, what vacuum level is required?

    1. 25 mm Hg absolute
    2. 10 inches of mercury
    3. 0 inches
    4. 4 inches
  3. What leak rate triggers repair for commercial refrigeration?

    1. 10 percent
    2. 20 percent per year
    3. 5 percent
    4. 30 percent
  4. Which of these is a major repair under Section 608?

    1. Reading pressures
    2. Adjusting a fan
    3. Cleaning a coil
    4. Removing the compressor
  5. After reaching the required recovery vacuum, what should you do before opening the system?

    1. Add refrigerant
    2. Wait to see if pressure rises
    3. Energize the compressor
    4. Remove the vacuum pump

Answer key

  1. D. R-410A. EPA lists R-410A among high-pressure refrigerants. 40 CFR 82.152 Definitions (Cornell LII)
  2. B. 10 inches of mercury. Medium-pressure appliances under 200 pounds must reach 10 inches of mercury vacuum with newer equipment. 40 CFR 82.156 (Cornell LII)
  3. B. 20 percent per year. Commercial refrigeration uses a 20 percent per year leak rate trigger. 40 CFR 82.157 Appliance maintenance and leak repair (Cornell LII)
  4. D. Removing the compressor. Removing the compressor, condenser, evaporator or coil is a major repair. 40 CFR 82.152 Definitions (Cornell LII)
  5. B. Wait to see if pressure rises. A pressure rise indicates that liquid refrigerant remains in the system or oil. EPA Section 608 Technician Certification Test Topics

Sources for this lesson

Lesson 6 of 6

Type III Low Pressure Service and Business Rules

This lesson covers Type III low-pressure chillers, refrigerant sales, certification details, records, and technology transition dates.

What you will learn

  • Describe low-pressure chiller recovery and recharging steps.
  • Explain refrigerant sales and reclamation exceptions.
  • Summarize Section 608 certification test and recordkeeping rules.
  • State the VRF GWP transition date.

Low-pressure chillers

A low-pressure refrigerant has a liquid saturation pressure below 45 psia at 104 F. Examples include R-11, R-123, R-113 and R-245fa.

Low-pressure appliances must be evacuated to 25 mm Hg absolute pressure. This level is the same whether the recovery equipment was made before or after November 15, 1993.

For a non-major repair on a low-pressure appliance that will not be evacuated to the atmosphere afterward, pressurize to no higher than 0 psig before opening.

If the refrigerant boils at or below 85 F at standard atmospheric pressure, do not use nitrogen that requires purging afterward. Use controlled hot water or a built-in heating device.

Heat the chiller oil to 130 F before removing it. The goal is to minimize refrigerant release when the oil comes out.

During refrigerant evacuation of a chiller, circulate or remove the water to prevent the water from freezing.

When recharging a low-pressure chiller, introduce vapor before liquid to prevent freezing of water in the tubes.

Excessive purging on a low-pressure chiller is a sign of leakage into the system. Under ASHRAE Standard 15, R-123 equipment rooms need a refrigerant sensor.

Sales and reclamation

It is the wholesaler's responsibility to determine whether a person claiming to represent a buyer really is an authorized representative. An employer can buy refrigerant by giving the wholesaler written evidence that it employs at least one certified technician.

Small cans of car air conditioner refrigerant, like R-134a, may be sold to uncertified buyers if the cans hold at most 2 pounds. They must have unique fittings and self-sealing valves.

Refrigerant sellers must keep invoices showing the purchaser's name, the date of sale and the quantity for three years.

Someone with only a Section 609 car air conditioning certification cannot buy refrigerant for stationary equipment. Only Section 608 certified technicians can buy stationary refrigerants, regardless of container size.

Used refrigerant normally must be reclaimed before it is sold. One exception is a transfer between a parent company and its subsidiary, or between subsidiaries of the same parent.

Certification tests and recordkeeping

Section 608 technician certification does not expire. Certifying programs must issue a wallet-sized identification card within 30 days of the test.

For Universal certification, the core test must be taken as a proctored exam, not open book. Mail-in Type I tests cannot count toward a Universal certification.

Closed-book Type I, II, III and Universal tests use a 70 percent passing score. Only mail-in Type I tests require a higher 84 percent.

A Universal test has 100 questions. It is 25 core questions plus 25 from each of the Type I, II and III areas.

An uncertified apprentice may work on refrigerant circuits only if a certified technician closely and continually supervises them. The apprentice must be registered with the U.S. Department of Labor's Office of Apprenticeship or a recognized State Apprenticeship Council.

A scrap yard can rely on a signed statement that a junked fridge's refrigerant was recovered. The statement must include the name and address of the person who recovered the refrigerant and the date of recovery.

Technology transitions

New VRF systems must have a GWP of 700 or less. If a higher-GWP system has all components manufactured or imported before January 1, 2026, it can be installed up to January 1, 2027.

A further extension to January 1, 2028 applies to buildings with a permit approved before October 5, 2023 that specified an HFC system.

Numbers to remember

ItemValueSource
Low-pressure limitbelow 45 psia40 CFR 82.152 Definitions (Cornell LII)
Low-pressure evacuation level25 mm Hg absolute40 CFR 82.156 (Cornell LII)
Oil heat target130 FEPA Section 608 Technician Certification Test Topics
Small MVAC can sales exemption2 pounds or lessEPA Refrigerant Sales Restriction
Seller invoice retention3 years40 CFR 82.154 Prohibitions (Cornell LII)
Universal test question count100 questions40 CFR Part 82 Subpart F Appendix D, certifying programs (Cornell LII)

Knowledge check

Choose an answer before reading the answer key.

  1. What is the required evacuation level for a low-pressure appliance?

    1. 4 inches of mercury
    2. 10 inches
    3. 0 inches
    4. 25 mm Hg absolute
  2. Before removing oil from a low-pressure chiller, to what temperature should you heat it?

    1. 100 F
    2. 150 F
    3. 85 F
    4. 130 F
  3. A small can of car AC refrigerant may be sold to an uncertified buyer if it holds at most how much?

    1. 20 pounds
    2. 2 pounds
    3. 15 pounds
    4. 5 pounds
  4. How long must refrigerant sellers keep invoices that show the buyer, date and quantity?

    1. Three years
    2. Five years
    3. One year
    4. Seven years
  5. Which breakdown of questions appears on a Universal certification test?

    1. 50 core only
    2. 25 core plus 25 each from Type I, II and III
    3. 25 core plus 75 Type I
    4. 100 Type II

Answer key

  1. D. 25 mm Hg absolute. Low-pressure appliances are evacuated to 25 mm of mercury absolute pressure. 40 CFR 82.156 (Cornell LII)
  2. D. 130 F. EPA's Type III topics say to heat the oil to 130 F before removing it. EPA Section 608 Technician Certification Test Topics
  3. B. 2 pounds. EPA exempts small cans designed to hold two pounds or less of car air conditioner refrigerant. EPA Refrigerant Sales Restriction
  4. A. Three years. Sellers must keep those records for three years. 40 CFR 82.154 Prohibitions (Cornell LII)
  5. B. 25 core plus 25 each from Type I, II and III. The Universal test has 25 core questions and 25 from each of the three type areas, totaling 100. 40 CFR Part 82 Subpart F Appendix D, certifying programs (Cornell LII)

Sources for this lesson

Practice checklist

  • โ˜ Review the six lessons and take the trivia deck one more time.
  • โ˜ Write out the recovery vacuum targets for Type I, Type II and Type III from memory.
  • โ˜ Drill the leak repair trigger rates and repair deadlines.
  • โ˜ Practice converting psig to psia by adding 14.7 psi.
  • โ˜ Have a study partner ask the knowledge check questions in each lesson.

Keep learning

  • Take the certification test with an EPA-approved certifying organization.
  • Keep your certification card and save any test results.
  • Review the EPA Section 608 Q&A page if you have a specific compliance question.
  • Practice recovery procedures with certified equipment under supervision.
  • Use the trivia deck to test your recall before your next certification.

How this guide was made

Aha Trivia wrote this guide from the 102 approved cards in Stuff Every HVAC Tech Should Know. Before a card is approved, two AIs check it, and code finds its quote on the source page.

DeepSeek V4 Pro wrote the lessons using only those cards. Codex (GPT-5.6) checked every line against the cards. Grok 4.20 settled the remaining disagreements. Lines that no check could confirm were removed. Every source link above comes from a checked card. Checked 2026-10-25.

Found a mistake? Tell us and we will fix it.

Practice what you learned

Aha Trivia turns the subject into short, scored questions. The guide and game are study tools, not official training or certification.

โ–ถ Play Stuff Every HVAC Tech Should Know Find another deck